Does spraying water on your roof cool your house, and is a roof mister worth the water?

Short answer

It depends on the insulation under the roof. Keeping a roof wet dropped its surface from about 141°F to under 102°F in a Lawrence Berkeley-led test, but the insulated ceiling below was only 0.3°C (0.5°F) cooler on average and the room barely changed. With no insulation, the same drop cuts heat through the ceiling by roughly 20,000 BTU an hour on a 1,500 sq ft house. Under R-19 or R-38 it saves cents a day while evaporating about 200 gallons or more.

Key takeaways

  • In the LBNL-led test on an insulated office roof in Japan, spraying held the roof surface near 37.5°C (99.5°F) against 60.8°C (141°F) dry, yet the average ceiling surface was only 0.3°C cooler. The authors concluded roof spraying "is not suitable" for well-insulated roofs.
  • A fine 5 micron mist on an older Baghdad house roof cut the outside roof surface by 1.71-15.5°C and the daily heat flux through the roof by 21.3-76.6%.
  • Spraying cuts about the same share of roof heat at any R-value. What insulation changes is the amount: on a 1,500 sq ft ceiling at peak, about 20,500 BTU/h with no insulation, 2,800 BTU/h under R-19 and 1,500 BTU/h under R-38 (MistGuide calculation).
  • Evaporating enough water to hold a dark roof wet in midday sun takes roughly 0.029 gallon per hour per square foot, about 215 gallons a day on 1,500 sq ft. The LBNL hose test used about four times that.
  • At $10 per 1,000 gallons and 17 cents per kWh, a kept-wet roof saves about $1.70 a day with no insulation, 23 cents under R-19 and 12 cents under R-38, against at least $2.15 of water.
  • The 47% cooling saving often quoted for roof spray comes from a night roof-spray storage system, which used 0.15-0.20 gallon per 1,000 BTU of cooling delivered: 10 to 14 times more cooling per gallon than daytime spraying even over an uninsulated ceiling.

Spraying water on your roof cools the roof a great deal and the house only as much as the insulation under the roof allows. In a test led by Lawrence Berkeley National Laboratory, keeping a roof wet held its surface under 39°C (102°F) while the dry roof beside it reached 60.8°C (141°F), and the insulated ceiling below was on average only 0.3°C cooler. With no insulation, the same cooler roof cuts the heat coming through a 1,500 sq ft ceiling by about 20,000 BTU an hour. Under R-19 or R-38 it saves cents a day while evaporating 200 gallons or more. So a roof mister is worth the water over a bare roof, and almost never over an insulated attic.

What does spraying actually do to a roof?

It drags the roof surface down toward the wet-bulb temperature, the same limit that governs any misting system (see how misting systems work). Three studies measured how far:

Measured effect of roof spraying, by study
Study and roofSprayRoof outside surfaceInside the building
Zhou et al. 2004 (LBNL-led), insulated steel-deck concrete office roof, Kitakyushu, Japan, August 2001Hose, roof kept wet continuouslyDry roof peaked at 60.8°C (141°F); sprayed roof held at 37.5°C, never above 39°C. Difference 20-25°C from 11:00 to 15:00Ceiling 0.3°C cooler on average, 0.5°C at most. Room peak 40.1°C vs 40.4°C
Jassim and Haris 2014, second-floor room of an older house, Baghdad, May-July 2012 (51 test days)12 nozzles, 0.006 in, 5 micron mist, high-pressure pump1.71-15.5°C lower over the day; 7.57°C lower on average at 2 p.m.Ceiling 0.5-1.91°C lower at 8 p.m.; daily heat flux through the roof 21.3-76.6% lower
Sharma et al. 2021, test cell with a cement roof, humid tropical climateAutomatic spray on a temperature thresholdAbout 5°C lower on averageLower indoor air temperature "cannot be guaranteed"

All three agree on the roof. They split on the room, and the split follows the roof construction. The LBNL building had rigid urethane insulation right under its waterproof layer, and the authors write that "spraying water did not affect room temperature," a result that "seems to be dependent on the room's ceiling insulation material." Their conclusion is blunt: roof spraying "did not significantly reduce cooling loads and required significant amounts of water," and it is "not suitable" for a building with well-insulated roofs, while being "clearly more effective" for poorly insulated ones.

How much heat does spraying keep out at R-0, R-19 and R-38?

The same share at every R-value, and a very different amount. Heat moves through a roof and ceiling roughly in proportion to the temperature difference across it divided by its total R-value. Spraying shrinks the temperature difference by the same fraction whatever sits underneath, so it cuts about the same percentage of roof heat on any house. Insulation decides what that percentage is a percentage of.

Peak heat through the ceiling with and without roof spray, room at 76°F (MistGuide calculation, steady state)
Ceiling insulation (whole path R-value)Dry roof, 141°FMist, roof 14°F cooler (127°F)Kept wet, roof 100°FCut on 1,500 sq ft, mistCut on 1,500 sq ft, kept wet
None (about R-3)21.7 BTU/h per sq ft17.08.07,000 BTU/h20,500 BTU/h (1.7 tons)
R-19 batts (about R-22)2.952.321.09950 BTU/h2,800 BTU/h
R-38 (about R-41)1.591.240.59510 BTU/h1,500 BTU/h

How the numbers are built: heat flow = (roof surface temperature minus 76°F) / R. The dry and kept-wet roof temperatures are the LBNL measurements. The mist column uses the Baghdad study's 7.57°C (13.6°F) average reduction at 2 p.m. The "about R-3" path is an assumption for roof deck, attic air space, drywall and air films with no insulation, added to the batt rating in the other rows. The 76°F room is the cooling setpoint in the ACEEE paper. Kept wet cuts 63% of the heat in every row and mist about 22%, both inside the Baghdad study's measured 21.3-76.6% range.

That is why both answers circulate. "Spraying cuts roof heat by half or more" is true, and it is what the percentage studies report. "Spraying does nothing" is what an insulated house measures, because 63% of 1.6 BTU per hour per square foot is about one BTU. The 1.7 tons in the top row is real cooling. The 1,500 BTU/h in the bottom row is an eighth of a ton.

The model leaves out roof mass, which delays and smooths the effect. Under the LBNL concrete roof, the ceiling difference peaked at 8 p.m., three hours after spraying stopped, seven or eight hours behind the roof, and lasted until 8 the next morning.

How much water does a roof mister use per day?

More than a 20-nozzle patio line running six hours, which uses about 180 gallons. Every gallon that evaporates absorbs about 8,700 BTU, and a wet roof in sun has a lot of heat to get rid of. Assume clear midday sun of about 1,000 W/m² (317 BTU per hour per square foot) with 80% absorbed by a dark roof, or about 250 BTU per hour per square foot. If evaporation carries all of it away, holding the roof wet takes 250 / 8,700 = 0.029 gallon per hour per square foot. Over five peak-equivalent hours on 1,500 sq ft, that is about 215 gallons a day.

That is a floor for the kept-wet case, because sprinklers lose water to runoff and wind. The LBNL team sprayed with a hose to keep the surface "always wet" and recorded 0.71-1.46 mL per second per square meter each hour on August 15, about 0.06-0.13 gallon per hour per square foot. Their seven-hour schedule adds up to about 25 litres per square meter, or 0.61 gallon per square foot: about 920 gallons a day on 1,500 sq ft.

Mist uses less water and does less. A fine mist that evaporates before it lands mostly cools the air over the roof, and the Baghdad roof's 7.57°C average peak drop is about a third of the LBNL wet roof's 20-25°C. Budget the nozzles' own flow, which the water use and cost calculator totals for a season, and see high-pressure misting systems for what a 5 micron line takes to build.

Is a roof mister worth the water?

Put the two tables together for a 1,500 sq ft house on a sunny day, using five peak-equivalent hours for both the heat and the water, an air conditioner moving 3 units of heat per unit of electricity (close to the 3.11 COP at 95°F in the AC condenser misting lab data), 17 cents per kWh, and the site's usual $10 per 1,000 gallons of water and sewer:

Kept-wet roof: heat kept out against water used, 1,500 sq ft, one sunny day (MistGuide calculation)
Ceiling insulationHeat kept outAC electricity savedValueWater, evaporation floor (215 gal)Water, LBNL hose rate (920 gal)Gallons per 1,000 BTU kept out (floor)
None (R-3)102,500 BTU10.0 kWh$1.70$2.15$9.202.1
R-1914,000 BTU1.4 kWh$0.23$2.15$9.2015
R-387,500 BTU0.7 kWh$0.12$2.15$9.2029

On an insulated house, the water costs roughly 9 to 77 times what the electricity saves. Even over a bare ceiling, the bill comes out slightly behind at the evaporation floor, and far behind at hose rates. Seen per gallon, only about 5.5% of the heat each evaporated gallon absorbs (477 of 8,700 BTU) would otherwise have reached a bare ceiling, and under 1% with R-19 or R-38. The rest would have left the roof by radiation and convection anyway: a wet roof mostly cools the sky.

The case where it pays is comfort, not dollars: a room directly under an uninsulated metal, wood or thin concrete roof, with no air conditioning to save. Cutting 63% of the ceiling heat there is the "poorly insulated" case LBNL says roof spraying suits. Baghdad's intervals help the water budget: continuous spray in the 11 a.m. to 4 p.m. peak, and 2 minutes on, 2 minutes off the rest of the day, which a cycle timer from misting controllers and timers can run. Insulation, as the Baghdad authors note, works in winter too, and roof spray only in the cooling season.

Where does the "47% cooling saving" come from?

From a different machine. Bourne and Carew's 1996 ACEEE paper describes a night roof-spray storage system on a new 27,500 sq ft office building in Los Angeles. It sprays the roof at night, when water is cooled by evaporation and by radiation to the night sky, returns the chilled water through the roof drains into a 15,000 gallon underground tank, and pumps it to cooling coils in four rooftop heat pumps the next day. Full-year simulations projected about 21,000 kWh a year of savings, about 47% of the base case cooling, and a 25 ton cut in required cooling capacity.

Its water use is the useful comparison: "monitored WhiteCap water use is 0.15 to 0.20 gallons/kBtu cooling delivered," or about 5,000-6,700 BTU of cooling per gallon. Daytime spraying over a bare ceiling, at the evaporation floor, manages 2.1 gallons per 1,000 BTU kept out: the night system gets 10 to 14 times more from each gallon. The difference is storage. The night sky does the cooling, and the tank holds it until the afternoon. The paper also notes that the spray keeps a white roof clean, which lowers daytime roof temperatures. A garden sprinkler on the shingles at 2 p.m. has none of that.

When does this advice not apply?

  • The heat-flux table is steady state. It ignores roof mass, attic ventilation and radiant barriers. Read it as the size of the effect, not a forecast for one house.
  • Humid air shrinks every number. A wet roof cannot fall below the wet-bulb temperature, so the drop is smaller in muggy weather, as misting in humid climates explains for patios. The cement test cell was in a humid tropical climate, and the Baghdad roof in dry heat.
  • Uninsulated walls are a separate question. The Baghdad team also misted the west wall, a low-insulated wall that became a cooling surface on most test days. This page covers roofs only.
  • Cheap or free water changes the bill, not the physics. Collected rainwater, as in graywater or rainwater for misting, lowers the dollar cost. It does not make an insulated ceiling pass more heat.

Spraying a roof for wildfire embers is a different job with different water math, covered in do wildfire roof sprinklers work.

Frequently asked questions

How long does it take for roof spraying to cool the room below?

Hours, under a heavy roof. In the LBNL-led test on an insulated concrete roof, the roof surface cooled as soon as spraying began, but the ceiling difference grew slowly, peaked at 0.5°C at 8 p.m., three hours after spraying stopped, and lasted until 8 a.m. the next day. The ceiling peak lagged the roof peak by seven or eight hours. A thin metal or wood roof with no insulation responds much faster.

Will spraying water on my roof damage it?

It can, if water stands or the roof stays wet into the evening. The Baghdad mist study found continuous spraying increased cooling but warned it can harm the building construction, especially in the evening and at high humidity, and recommended running 2 minutes on and 2 minutes off outside the 11 a.m. to 4 p.m. peak. Every gallon that evaporates also leaves its dissolved minerals on the roof, so hard water builds a crust over a season.

Is roof spraying worth it in a house with no air conditioning?

It can be, if there is no insulation between the roof and the room. Then the money math does not apply and the comfort does: keeping the roof wet cuts the heat coming through the ceiling by about 60%, which is the case the LBNL authors say roof spraying is clearly more effective for. If the attic is insulated, the room will barely notice, and a fan or shading does more.

Does spraying the roof at night work better?

For cooling, yes, but only with somewhere to store the cold. The night system in the ACEEE paper sprays the roof after dark, collects the water chilled by evaporation and the night sky in a 15,000 gallon tank, and pumps it through cooling coils the next afternoon. Spraying a roof at night with no tank cools the roof when the house needs it least.

Sources and further reading

Figures on this page are cross-checked against the shared planning values in our research methodology. Where manufacturers publish different numbers, your equipment's data sheet takes precedence.

Spotted an error or an outdated figure? Tell us and see how we handle corrections.